MICROSET CONTROLS
 

 
 

Ultrasonic Level Transmitter - MS ULT 311

 
Ultrasonic Level Transmitter - MS ULT 311
 

SALIENT FEATURES

• Non contact type level measurement.
• 2 wire operation.
• Integral LCD Display
• Self diagnostic function i.e. Error message are displayed.
• Automatic temperature compensation.
• Instrument configuration settings are password protected.
• Accuracy 0.25% of F. S.
• Compact size & easy maintenance.
• Reliable & cost effective system.
• Software calibration.

DESCRIPTION
MicroSet series MS ULT - 311 is a 4 wire Ultrasonic Level Transmitters specially designed for non contact type level measurement.
Ultrasonic level measurement is based on the time required by ultrasonic pulses to travel from sensor & surface of liquid & back to sensor.
Ultrasonic level transmitters are the best for applications such as slurries, corrosive liquids & waste water. The transmitter provides 4-20
mA DC continuous output with local indication through LCD. The measuring range is available from 0.6 to 8 meter.

 
 
TECHNICAL SPECIFICATIONS
 
 
Measuring Range
:
0.6 to 8 mtr
Type of Output
:
4 - 20 mA DC, 2 wire
Power Supply
:
24 V DC, External
Power Consumption
:
< 500 mW
Dead Band
:
0.6 mtr
Display
:
8 x 1 LCD (4 digit for Level)
Accuracy
:
+/- 0.25% of F. S.
Operating Temperature
:
-30 to 80°C
Operating Pressure
:
Atmospheric
Beam Angle
:
< 7°
Response Time
:
< 500 mSec
Measuring Frequency
:
25 Khz
Temperature Coefficient
:
+/- 0.01% per°C
Enclosure
:
Weather-proof, IP-65
Process Connection
:
2” BSP Threaded
Mounting
:
Top of the tank
Weight
:
1.5 kg
Operating Conditions
:
Temperature 0 to 55 C / Humidity 5 to 95% non condensing
 
NOTE : Process temperature & pressure exceeding specified limits, kindly consult with factory.
 
 
           
     
   
 
Home

About us

Contact us

Enquiry

Sitemap
 
 
     
Industrial pH Sensor MS pH 01 / MS pH 02 / MS pH 04, MS pH 07, • pH Sensor – Industrial – HF Series MS pH 22 / HF / Pt 100, • Industrial pH Sensor - MS pH 36 – Flat (Origin USA), • pH Indicator MS pH 19, • pH Controller MS pH 27 / MS pH 27W, • pH Transmitter MS pH 27B / MS pH 18T, • Lab / Bench Meter MS pH 616 / MS pH 644, MS 324 / MS pH 816 / MS 9535, • pH Sensor Housing for Fermentor Model 330, • pH Flow Cell, • Industrial ORP Sensor with Platinum Tip MS ORP 01 / MS ORP 02 / MS ORP 36, • ORP Indicator MS ORP 19, • ORP Controller MS ORP 27 Panel Mounted, • ORP Controller MS ORP 27W Field Mounted
MICROSET INSTRUMENTATION & CONTROLS
A
:
102, Chinmay, 1103 / A / 10, Model Colony, Lakaki Road, Shivaji Nagar,
Pune - 411 016. Maharashtra, INDIA.
T/F
:
M
:
E
:
 
 
home contact us sitemap